JE-H st H…Bd FE180 E90

Place of use

These cables are used in fire alarm and security systems, which continue functioning during an instance of fire. (They are used at places where a lot of people can be found such as subways, tunnels, shopping centers, hospitals, airports, hotels, residential buildings, industrial facilities etc.)


This type of cables is halogen-free, has flame -retarder and low smoke density.

Structure

Inner Conductor

Electrolytic Solid Copper Wire, Class 1
EN 60228, IEC 60228, VDE 0295

Insulation

Mica Tape + Ceramic Silicone Compound,
VDE 0815 Colour Code

Stranding

Pairs in Layers

Seperator

PES Tape and Glass Fiber Tape

Screen

AL-PES Tape and Tinned Copper Drain Wire.

Outer Sheath

HFFR Compound EN 50290-2-27, RAL 2003 Orange


Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C

Technical Info


LOOP
RESISTANCE
INSULATION
RESISTANCE (min)
MUTUAL CAPACITANCEOPERATING
VOLTAGE
BENDING RADIUSTEST VOLTAGETEMPERATURE RANGE

0,6 mm
0,8 mm
1,0 mm
1,5 mm²
2,5 mm²
Ω/km
130
73,2
44,6
24,6
15,1
MΩxKm
100
nF/km
100
V
300
10X D0,6/0,8 mm : 800 V
>1,0 mm : 1000 V
-40ºC+70ºC

Catalog Info